IAPMO RESEARCH AND TESTING, INC.

5001 E. Philadelphia Street, Ontario, CA 91761-2816 • (909) 472-4100 • Fax (909) 472-4244 • www.iapmo.org





CERTIFICATE OF LISTING

IAPMO Research and Testing, Inc. is a product certification body which tests and inspects samples taken from the supplier's stock or from the market or a combination of both to verify compliance to the requirements of applicable codes and standards. This activity is coupled with periodic surveillance of the supplier's factory and warehouses as well as the assessment of the supplier's Quality Assurance System. This listing is subject to the conditions set forth in the characteristics below and is not to be construed as any recommendation, assurance or guarantee by IAPMO Research and Testing, Inc. of the product acceptance by Authorities Having Jurisdiction.


 

Effective Date : October 2009      
Void After: October 2010
     
Product: Earthquake Actuated Automatic Gas Shut-off Valves 
File No. 3266
     
Issued To : LITTLE FIREFIGHTER CORPORATION
204 S. CENTER STREET
SANTA ANA, CA  92703
     
IDENTIFICATION:  The devices shall be permanently marked or permanently labeled with manufacturer's name or address, model number, pressure rating and direction of flow if applicable, the symbol of the organization which tested the device for compliance with ASCE 25-97, and "ASCE 25-97" marking. The product shall also bear the UPC® certification mark.

All devices shall also have installation and resetting warnings affixed to the devices with a tag and on the device shipping carton:

Installation Warning

Warning! This device must be installed by a qualified installer in accordance with the manufacturer’s installation instruction; if improperly installed, failure to function as intended or unwarranted interruption of gas service could result.

Resetting Warning

Following actuation of this device, reset the device and restore service only after a qualified person has verified no gas leak exits.

Note: All metal marking material shall be rustproof.
     
CHARACTERISTICS:  Earthquake actuated automatic gas shutoff devices having gas pressure rating of 0.5 psi (3.4 kPa) up to and including 60 psi (414 kPa) with capability of operating at ambient temperatures of -10° F to 150°F (-23°C to 66° C), unless manufacturer specifies lower minimum or higher maximum operating temperature ranges. The devices are intended to be used in single-family or multi-family structure of three stories or less. To be installed in accordance with manufacturer’s instructions, and in a manner as to be sensitive to earthquake ground motions that might result from the dynamic response of structures, equipment, or other appurtenances, and the latest edition of the Uniform Plumbing Code. When Installed, Pressure drop from meter to any outlet shall not be more than 0.5" water column.

Products comply with the applicable sections of the latest edition of the Uniform Plumbing Code® and the International Plumbing Code®.  Manufactured in compliance with ASCE 25-97.

Products listed on this certificate have been tested by an IAPMO R&T recognized laboratory. This recognition has been granted based upon the laboratory’s compliance to the applicable requirements of ISO/IEC 17025.

     

MODELS:

Little Firefighter

AGV-75  (Mechanically Activated) Utilitron - EIC300-R
AGV-100
AGV-150
AGV-125
AGV-200
VAGV-75
VAGV-100
VAGV-125
VAGV-125HF
VAGV-150
VAGV-150HP
VAGV-200
VAGV-200HP



   
ADDITIONAL COMPANIES:
 
ADDITIONAL COMPANY INFO:

ChairmanExecutive Director